Seaward PrimeTest 250+ PAT Tester
IET 5th Edition and BS EN50699 Compliant
The PrimeTest 250+ portable appliance tester is battery powered and handheld to allow for fast and efficient testing with clear PASS/FAIL indication and test result values. It has a comprehensive range of mains and battery powered tests, data storage and label printing features.
– Selectable 250V/500V Insulation test
– Mains leakage testing
– Portable RCD Testing
– Variable Earth Continuity and Leakage pass/fail limits
1.000,00 د.إ
IET 5th Edition and BS EN50699 Compliant
The PrimeTest 250+ portable appliance tester is battery powered and handheld to allow for fast and efficient testing with clear PASS/FAIL indication and test result values. It has a comprehensive range of mains and battery powered tests, data storage and label printing features.
– Selectable 250V/500V Insulation test
– Mains leakage testing
– Portable RCD Testing
– Variable Earth Continuity and Leakage pass/fail limits
More about the PrimeTest 250+
Enabling simple, professional and fast PAT testing, this versatile tester features all of the required tests of the IET 5th Edition Code of Practice and BS EN50699, along with USB download. It is also fully compatible with the Test n Tag Pro serial printer for quick and easy label printing without any setup required – just plug and print.
Using Seaward’s free datalogger program and pressing a single download key allows test result data to be quickly and easily transferred from the PrimeTest 250+ to PC at the press of a button. Data is downloaded in a simple CSV spreadsheet format for your PAT records or alternatively the CSV data can be imported directly into Seaward’s PATGuard 3 software for more enhanced record keeping, reporting and certification.
Seaward’s unique ‘ZAP’ technology ensures that earth continuity measurements are accurate in situations where other testers struggle to provide reliable measurements, such as measuring through rust, limescale and other surface contamination.
Built in Britain and used by 1,000’s of organisations every day.
| Feature | Details |
|---|---|
| Data Storage | Up to 999 test records |
| Insulation Test | Selectable 250V / 500V DC |
| Earth Continuity Test | 200mA minimum into 2Ω |
| Mains Leakage Testing | Yes |
| Portable RCD Testing | Yes |
| Earth Continuity Limits | Variable PASS/FAIL limits |
| Leakage Limits | Variable PASS/FAIL limits |
| 3-Phase Leakage Testing | Yes, with optional 3-phase adaptor |
| USB Data Download | Yes |
| Data Export | CSV format |
| Label Printing | Test n Tag Pro compatible |
| Earth Continuity Technology | Seaward ZAP technology |
| Warranty | 2 Years |
| Specification | Value |
|---|---|
| Earth Continuity Test Current | 200mA minimum into 2Ω |
| Earth Continuity Test Voltage | 9V DC nominal |
| Earth Continuity Display Range | 0.01–19.99Ω |
| Earth Continuity Pass Values | 0.1Ω / 0.2Ω / 0.3Ω |
| Insulation Test Voltage | 250V / 500V DC @ 1mA nominal |
| Insulation Resistance Display Range | 0.01–19.99MΩ |
| Insulation Pass Value – Class I | 1.0MΩ |
| Insulation Pass Value – Class II | 2.0MΩ |
| Equivalent Leakage Range | 0.1–19.99mA |
| Equivalent Leakage Pass Values | 0.5 / 3.5 / 5.0mA |
| IEC Lead Test Voltage | 5V DC nominal |
| Protective Conductor Current Range | 0.15–9.99mA |
| Touch Current Range | 0.10–5mA |
| 3-Phase Leakage Current Range | 0.10–9.99mA |
| RCD Test Current | 30 / 150mA rms sinusoidal |
| RCD Measuring Range | 0–500ms |
| Power Socket Input Voltage | 225–254V AC, max. 13A (UK) |
| Memory | Up to 999 test records |
Similar Products
Reviews
There are no reviews yet.