Seaward PrimeTest 50 PAT Tester
IET 5th Edition Code of Practice Compliant
The PrimeTest 50 portable appliance tester is battery powered and handheld to allow for fast and efficient testing with clear PASS/FAIL indication. A simple range of tests are selected at the push of a button to test earthed equipment, double insulated equipment, mains cords and leads.
– Selectable 250V/500V Insulation test
– Simple push button operation
– Battery operated
– Long battery life
1.000,00 د.إ
The PrimeTest 50 is a great choice for those needing one of the most reliable and easy to use PAT testing machines available.
This PAT tester is ideal for those testing smaller quantities of equipment with an emphasis on simplicity and ease of use. Perfect for simple equipment checks or where enhanced visual inspections are being carried out by Staff.
The PrimeTest 50 is capable of testing Class 1, Class 2, Cables and IT equipment, providing clear PASS/FAIL indication on a large LCD display.
Seaward’s unique ‘ZAP’ technology ensures that earth continuity measurements are accurate in situations where other testers struggle to provide reliable measurements, such as measuring through rust, limescale and other surface contamination.
Three test buttons allow the user to select the appropriate test and an internal smart circuit identifies if an appliance or an extension cord is connected.
The PrimeTest 50 also incorporates a mains outlet test and is supplied with all necessary accessories to help organisations perform PAT Testing with a minimum of fuss.
Built in Britain and used by 1,000’s of organisations every day.
| Feature | Details |
|---|---|
| Operation | Simple push-button operation |
| Test Sequences | Class I, Class II & Cord |
| Earth Continuity Test | 200mA |
| Insulation Test | Selectable 250V / 500V DC |
| IEC Lead Test | Yes |
| Mains Supply Check | Yes |
| Display | LCD with clear PASS/FAIL indication |
| Earth Continuity Technology | Seaward ZAP technology |
| Power Source | Battery |
| Battery Type | 6 × AA disposable cells |
| Portability | Handheld |
| Specification | Value |
|---|---|
| Earth Continuity Test Current | ±200mA DC |
| Earth Continuity PASS/FAIL Threshold | 0.2Ω |
| Insulation Test Voltages | 250V / 500V DC |
| Insulation PASS/FAIL Threshold | 1MΩ / 2MΩ |
| IEC Lead Test | Earth Continuity, Insulation Resistance & Live/Neutral Checks for open circuit, short circuit and crossed wiring |
| Power Socket Input Voltage Range | 230V +10% / −15% AC |
| Power Socket Indicators | Phase–Earth, Phase–Neutral & Neutral–Earth Voltage |
| Power Source | 6 × AA disposable cells |
| Weight | 800g |
| Dimensions | 110 × 55 × 270mm |